Description
At a glance
If you're still running T12s, this ballast has your back.
Designed for 120V systems, it powers 1–2 lamps with instant start tech for quick, efficient ignition. With Class P thermal protection, auto-restart, and ICES-005 compliance, it's a solid choice for commercial, retail, or industrial spaces where fluorescent lighting is still holding the line.
Quiet. Reliable. Doesn’t overcomplicate things.
✅ You need this if:
-
You’re using 30W to 75W T12 fluorescent tubes
-
You need a 120V ballast with instant start for rapid lamp ignition
-
Your installation requires thermal protection and auto-restrike
-
You want a normal ballast factor and consistent output
-
You’re working in Canada and need ICES-005 compliance
❌ You don’t need this if:
-
You’ve upgraded to T5, T8, or LED systems
-
You’re working with a 347V electrical supply
-
You need dimming or advanced controls — this one keeps it simple
-
You’re planning to test and return it (installed ballasts = final sale)
📊 Technical Specs
-
Ballast Type: Electronic
-
Start Method: Instant Start (IS)
-
Lamp Connection: Parallel
-
Input Voltage: 120V
-
Frequency: 50/60 Hz
-
Ballast Factor: 0.86 – 1.02
-
Max Case Temp: 75°C
-
Thermal Protection: Class P
-
OCV: 600V
-
Sound Rating: A
-
Auto-Restart: Yes
-
Certifications: cULus Listed, ICES-005 Compliant
-
Warranty: 5-Year Limited
💡 Performance by Lamp Type:
Lamp Type | # of Lamps | Ballast Factor | Power (W) | Current (A) | Start Temp (°C/°F) | B.E.F. |
---|---|---|---|---|---|---|
F96T12 (75W) | 2 | 0.86 | 133 | 1.12 | -18°C / 0°F | 0.65 |
F96T12/ES (60W) | 2 | 0.88 | 113 | 0.95 | -18°C / 0°F | 0.78 |
F84T12 (70W) | 2 | 0.88 | 122 | 1.04 | -18°C / 0°F | 0.72 |
F72T12 (57W) | 2 | 0.90 | 107 | 0.92 | -18°C / 0°F | 0.84 |
F64T12 (52W) | 2 | 0.90 | 93 | 0.78 | -18°C / 0°F | 0.97 |
F60T12 (50W) | 2 | 0.90 | 85 | 0.72 | -18°C / 0°F | 1.06 |
F48T12 (40W) | 2 | 0.92 | 76 | 0.67 | -18°C / 0°F | 1.21 |
F48T12/ES (30W) | 2 | 0.92 | 64 | 0.56 | -18°C / 0°F | 1.44 |
🔧 Installation Notes:
-
Lamp Compatibility: 30W–75W T12 fluorescent lamps
-
Voltage: 120V
-
Start Temp: -18°C (0°F)
-
Thermal Cutoff: Max case temp 75°C
-
Sound Rating: A — quiet for classrooms, offices, etc.
⚠️ Important Notice:
-
Confirm lamp type and voltage before install
-
Installed ballasts cannot be returned
-
Follow all electrical codes and spec sheets — your future self will thank you